![Pulsar ULTRA 5 Скачать руководство пользователя страница 172](http://html1.mh-extra.com/html/pulsar/ultra-5/ultra-5_instruction-manual_1624513172.webp)
Page 164
Options
Description
5=Step Time
Step Time Control allows relays to be used to
control a device, such as a motorised valve or
gate, in order to maintain the level within two
predetermined points. Relays will
energise
“
ON
” when Step Time condition is in effect
and
de-energises
“
OFF
” when Step Time
goes off. One relay will be required to control
an increase in level, (‘open’ the device) and a
second relay is required to control a decrease
in level, (‘close’ the device).
Alarm ID
(P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2) is used to assign
the relay to control either the
open
or
close
condition. Step Time Control relay requires
three setpoints. The first set point (P2
1
3, 2
2
3,
2
3
3, 2
4
3, 2
5
3) determines the
level
, at which
the relay is to be activated, (N.B. level
setpoint for
open
relay,
increase
the level,
must be
lower than
the setpoint for the
close
relay,
decrease
the level). The relay will
energise
“
ON
” after the
Limit time
that is set
in Relay
Setpoint 3
(P2
1
5, 2
2
5, 2
3
5, 2
4
5,
2
5
5). And turns “
OFF
”,
de-energises
, after
the
Drive Period
that is set in Relay
Setpoint
2
(P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4).
When
Ultra Wizard = 3 Flow
2 = Step Time
6 = Differential Control
Relay will
energise
“
ON
” when a differential
condition is in effect and,
de-energise
“
OFF
”
when the differential conditions cease. Two
setpoints are required,
Differential
control
“
ON
”, (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3) and
Differential
control, “
OFF
” (P2
1
4, 2
2
4, 2
3
4,
2
4
4, 2
5
4).
This allows the relay to be used to activate a
device as a result of a differential level,
between two points e.g. operate a rake on a
screen.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...