Page
79
To program the unit for
Example 1 Level Monitoring with alarms
by
using the
Quick Setup
menu proceed as follows.
If required access the
Program Mode
Key in the
passcode
1997
and press
ENTER
Using the ‘right’ arrow key go to the
Quick Setup
menu press
ENTER
and
as prompted, by the questions, select the relevant option and
ENTER
.
Question
Option
Level, Pump Up/Down or
Differential
1 = Level App.
No. of Alarms
2 = 2 Alarms
Type Alarm 1
1 = High
Alarm No 1
1 = Set Relay 1
Type Alarm 2
2 = Low
Alarm No 2
2 = Set Relay 2
Xducer (P101)
2 = dB6
Material (P102)
1 = Liquid
Measnt Units (P104)
1 = metres
Empty Level (P105)
3.5 (metres)
Span (P106)
2.8 (metres)
Programming is now complete and the unit can be returned to the run mode,
press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
,
and the Advanced 5 will return to the
Run Mode
.
Note
If relay setpoints do not meet the exact requirements of the application, they
can be modified to suit by pressing ENTER when, “For More Options Hit
Enter”, is displayed and entering new values to relay setpoints as required.
Alternatively, the relevant relay setpoint can be accessed either by the main
menu system or directly via parameter number and changed as necessary.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...