Page 152
Alarms
P210, 220, 230, 240, 250 =1 (Alarm)
The
second parameter
for each relay determines the
function
of the alarm.
P211, P221, P231. P241, P251 - Relay Function
This parameter defines what
function
the
alarm
will respond to as follows.
Option
Description
0= Off (Default)
Relay will not operate.
1= Level
Alarm is based on the level in the vessel, and the
type of level alarm (P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2) and
two setpoints must be set (P2
1
3, 2
2
3, 2
3
3, 2
4
3,
2
5
3 & P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4). Setpoints are
entered in Display Units or % of span as referenced
to Empty Level
*
.
2= Rate of Change
Alarm is based on the rate of change of level in the
vessel, and the type of rate of change alarm (P2
1
2,
2
2
2, 2
3
2, 2
4
2, 2
5
2) and two setpoints must be set
(P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3 & P2
1
4, 2
2
4, 2
3
4, 2
4
4,
2
5
4). Setpoints are entered in Display Units per
minute or % of span per minute and a negative
value should be entered for a Rate Alarm on a de-
creasing level, and a positive value for an
increasing level.
3= Temperature
Alarm is based on the temperature, and the type of
temperature alarm (P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2) and
two setpoints must be set (P2
1
3, 2
2
3, 2
3
3, 2
4
3,
2
5
3 & P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4). The temperature
used depends on the temperature source selected
(P852). Setpoints are entered in
o
C.
4= Loss of Echo
Alarm is raised if the
Failsafe
Timer
(
P809
)
expires. No setpoints are required.
5= Loss of Clock
Alarm is raised if the real time clock fails. No
setpoints are required.
When Ultra Wizard =2 Pump Differential
and
Pump Efficiency Enabled
6= Pump Efficiency
When Pump Efficiency is enabled, Alarm is
based on the Efficiency of the pump which is
allocated to the relay I.D. (P2
1
2, 2
2
2, 2
3
2, 2
4
2,
2
5
2) and two setpoints must be set (P2
1
3, 2
2
3,
2
3
3, 2
4
3, 2
5
3 & P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4).
Setpoints are entered in %.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...