![Pulsar ULTRA 5 Скачать руководство пользователя страница 177](http://html1.mh-extra.com/html/pulsar/ultra-5/ultra-5_instruction-manual_1624513177.webp)
Page
169
Miscellaneous
P210, 220, 230, 240, 250 = 4 (Miscellaneous)
When a relay is set to be a
miscellaneous relay
, the
second parameter
determines its
function
.
P211, P221, P231, P241, P251 - Relay Function
,
This function allows the relay to work in relation to a clock or a specific
event and will be set to activate in relation to Real Time.
Options
Description
0 = Off (Default)
Relay
Off de-energised
1 = Clock
Relay will
energise ON
at a specified time each
day as set in Relay Setpoint 1 (P2
1
3, 2
2
3, 2
3
3,
2
4
3, 2
5
3). And turns
OFF
,
de-energises
, after
the specified-On Time period as set in Relay
Setpoint 2 (P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4)
When Ultra Wizard = 2 Pump/Differential
and
Pump Volume Enabled P205 = 1
or
When Ultra Wizard = 3 Flow
2 = Totaliser
Relay will energise ON momentarily each time
the specified volume has passed as set in Relay
setpoint 1 (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3), this
parameter sets the multiplication factor which
will be applied to the on board totaliser (P820) to
determine the switch point of the relay. E.g. if the
totaliser is set to totalise in cubic metres and the
relay is required to provide a closure every
10,000 litres Relay setpoint 1 would be set to 10.
Relay setpoint 2 (P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4) is
used to select the time the relay will remain
closed in seconds.
Important Information
When using a Relay to control a device at a specified time of day ensure that
the
Time
P932
is set correctly. And if required, enable
Daylight Saving
for
the appropriate time difference
P970 – P979
.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...