Page
213
Stability Parameters
Damping
Damping is used to damp the display, to enable it to keep up with the
process but ignore minor surface fluctuations.
P870 Fill Damping
This parameter determines the
maximum rate
at which the unit will
respond to an
increase in level
. It should be set slightly higher than the
maximum vessel fill rate.
Default = 10m/min
P871 Empty Damping
This parameter determines the
maximum rate
at which the unit will
respond to a
decrease in level
. It should be set slightly higher than the
maximum vessel empty rate.
Default = 10m/min
Indicator
P872 Fill Indicator
This parameter determines the rate at which the LCD
fill
indicator activates.
Default = 10m/min
P873 Empty Indicator
This parameter determines the rate at which the LCD
empty
indicator
activates.
Default = 10m/min
Rate
P874 Rate Update
This parameter determines the way in which the rate is calculated. If set to
continuous
(
P874
=
0
), then the rate is calculated and displayed
continuously, i.e. any change seen from shot to shot is calculated and
displayed, but if set to use
values
P874
=
1(Default)
then the
values
set in
P875
and
P876
are used to calculate and display the rate.
P875 Rate Time
This parameter is the period (in seconds) over which the material level rate
of change is averaged before the
Rate
Value
(
P877
) is updated. If the
Rate
Distance
(
P876
) is exceeded before the
Rate Time
(
P875
) has expired then
the
Rate Value
(
P877
) will be updated immediately.
Default = 60sec.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...