Page 160
Pump Duty
Description
9 = Service Ratio Standby
When a service ratio duty is being used,
on all other pumps in use, the standby
pump can be started on a ratio basis
only, when it will assume the setpoints
of the next pump to start. The third
setpoint (P2
1
5, 2
2
5, 2
3
5, 2
4
5, 2
5
5) is
used to set the service ratio.
10 = Two Pump Sets
There are four pumps. Two rotate their
start-up sequence with each other. If the
two pumps cannot keep up, the level rise
to the setpoints of the other two pumps
which take over and rotate their
sequence with each other.
Important Information
The pumps are started and stopped at the “ON” and “OFF” setpoints. To
pump down
(reduce level) then set “ON” higher than “OFF”. To
pump up
(increase level) then set “ON” lower than “OFF”.
The
third parameter
for each relay determines the pump group. You can
have two groups of pumps, and all similar duties within a group will operate
together.
P212, P222, P232, P242, P252 - Relay Pump Group
By
default
, all pump groups are set to
1
, but if you want to have another
group, then set this parameter to 2, for each pump relay that should operate
together as part of a second group.
The
fourth parameter
and the
fifth parameter
for each relay set the
pump
“
ON
” and “
OFF
” points, which are entered in
Measurement units P104
.
For
pump down
the “
ON
” is set
higher than
“
OFF
”. For
pump up
then
“
ON
” is set
lower than
“
OFF
”. See the appropriate
pump duty,
function
table (
P212, 222, 232, 242, 252
) for further information.
P213, P223, P233, P243, P253 - Relay Setpoint 1
This parameter determines the “
ON
” point of the pump.
P214, P224, P234, P244, P254 - Relay Setpoint 2
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...