![Pulsar ULTRA 5 Скачать руководство пользователя страница 163](http://html1.mh-extra.com/html/pulsar/ultra-5/ultra-5_instruction-manual_1624513163.webp)
Page
155
The
fourth parameter
and the
fifth parameter
for each relay set the
Alarm
“
ON
” and “
OFF
” points. For a
high alarm
the “
ON
” is set
higher
than
“
OFF
”. For
low alarm
then “
ON
” is set
lower than
“
OFF
”. See the
appropriate
alarm ID,
table (
P212, 222, 232, 242, 252
) for further
information.
When P211, 221, 231, 241, 251 = 4 (Loss of Echo)
or
5 (Loss of Clock)
This parameter has no function and will not be displayed
P211, 221, 231, 241, 251 = 1 (Level), 2 (Rate of Change), 3 (Temp.)
or
6 (Efficiency)
P213, P223, P233, P243, P253 - Relay Setpoint 1
Determines the “
ON
” or “
OFF
” point for the alarm according to the
ID
selected.
P214, P224, P234, P244, P254 - Relay Setpoint 2
Determines the “
ON
” or “
OFF
” point for the alarm according to the
ID
selected.
Important Information
Setpoints
are entered in values according to the
function
selected.
Level -
entered in Measurement Units P104 or % of span as referenced
to Empty Level.
Rate of Change -
entered in Display Units per minute or % of span per
minute. For an alarm on an increasing level enter setpoints as a positive
value, for an alarm on a decreasing level enter setpoints as a negative
value.
Temperature -
entered in ºC.
Efficiency
– entered in % value of efficiency.
See the appropriate
alarm function
, table (
P211, 221, 231
) for further
information.
*
To set figures in % press the
hot key to show and enter % figure
relative to empty level.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...