The default values used for determining the
relay setpoints
, when setting
Alarm
and
Control
relays, via the
Quick Setup
menu are entered as a % of
span and are as follows.
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Down
One
Control 1
80%
20%
Cntl. Down
Two
Control 1
Control 2
80%
70%
20%
20%
Cntl. Down
Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
Cntl. Down
Four
Control 1
Control 2
Control 3
Control 4
80%
70%
60%
50%
20%
20%
20%
20%
Cntl. Down
Five
Control 1
Control 2
Control 3
Control 4
Control 5
80%
70%
60%
50%
40%
20%
20%
20%
20%
20%
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Up
One
Control 1
20%
80%
Cntl. Up
Two
Control 1
Control 2
20%
30%
80%
80%
Cntl. Up
Three
Control 1
Control 2
Control 3
20%
30%
40%
80%
80%
80%
Cntl. Up
Four
Control 1
Control 2
Control 3
Control 4
20%
30%
40%
50%
80%
80%
80%
80%
Cntl. Up
Five
Control 1
Control 2
Control 3
Control 4
Control 5
20%
30%
40%
50%
60%
80%
80%
80%
80%
80%
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...