Page
85
This will operate as follows, when the level rises on the upstream side
and/or the level on the downstream side falls, resulting in a differential of
0.14m, (anywhere within the working span), indicating that the screen is
blocked, relay 1 will come on and operate the rake. Once the level on the
inflow has decreased and the differential level falls to 0.03m relay 1 will
switch off the rake.
Should the level on the upstream side rise, for any reason, to a level of
2.38m, relay 2 will operate to give a high alarm, once the level has fallen
back to 2.24m the alarm will go off. A falling level in the downstream side,
for any reason, will operate relay 3 at 0.28m giving an alarm for low level,
once the level has risen again to a value of 0.42 m relay 3 will reset.
To program the Advanced 5 for
Example 2 Differential Control
by using
the
Quick Setup
menu proceed as follows.
Access the
Program Mode
Key in the
passcode
1997
and press
ENTER
At the
Quick Setup
menu press
ENTER
and as prompted, by the questions,
select the relevant option and
ENTER
.
Question
Option
Level, Pump Up/Down or
Differential
4 = Differential
No. of Control relays
1 = 1 Control
Control No. 1
1 = Set to Relay 1
Control
1 = Diff. Control
No. of Alarms
2 = 2 Alarm
Type Alarm 1
1 = High Alarm
Alarm No.1
2 = Set to Relay 2
Alloc. AL. 1
2 = Xducer 1
Type Alarm 2
1 = Low Alarm
Alarm No. 2
3 = Set to Relay 3
Alloc. AL. 2
3 = Xducer 2
Xducer (P101)
2 = dB6
Measnt Units (P104)
1 = metres
Empty Level (P105)
3.5 (metres)
Span (P106)
2.8 (metres)
Programming is now complete and the unit can be returned to the run mode,
press
CANCEL
until
Run Mode?
Is displayed on the LCD press
ENTER
,
and the Advanced 5 will return to the
Run Mode
.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...