P212, P222, P232, P242, P252 - Relay Alarm ID/Pump Group
,
When Ultra Wizard = 2 Pump Differential
P211, 221, 231, 241, 251 = 1, 2, 3 or 6
This parameter has no function and will not be displayed.
P211, 221, 231, 241, 251 = 4 (Flush Valve)
If the relay is selected for Flush Valve/Pump
,
then this parameter is used to
determine to which pump the Flush function is assigned. Enter the
relay
number to which the assigned pump is connected
.
P211, 221, 231, 241, 251 = 5 (Step Time)
If the relay is selected for Step Time
,
then this parameter is used to assign
the relay to the 0 =
Open
condition (increase level) or 1 =
Clos
e condition
(decrease level).
When Ultra Wizard = 3 Flow
P211, 221, 231, 241, 251 = 2 (Step Time)
If the relay is selected for Step Time
,
then this parameter is used to assign
the relay to the 0 =
Open
condition (increase level) or 1 =
Clos
e condition
(decrease level).
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...