Page 146
P103 Input 2 (Optional)
The 4-20 mA input is available as an option (Consult Pulsar for details of
availability), and can be used to replace the transducer for applications
where an ultrasonic transducer cannot be used.
Use this parameter to set the second input device when using in Average or
Differential Mode, and
P101 Transducer =
1
(Optional Auxiliary Input).
Option
Description
0= None (Default)
Second Transducer input not required.
1 = dB3
Transducer is a dB3. Range 0.125 to 3.00 metres
2 = dB6
Transducer is a dB6. Range 0.3 to 6.00 metres
3= dB10
Transducer is a dB10. Range 0.3 to 10.00 metres
4= dB15
Transducer is a dB15. Range 0.5 to 15.00 metres
5= dB25
Transducer is a dB25. Range 0.6 to 25.00 metres
6 = dB40
Transducer is a dB40. Range 1.2 to 40.00 metres
7 = dBS6
Transducer is a dBS6. Range 0.2 to 6.00 metres
8 = dBMach3
Transducer is a dBMach3 Range 0.0 to 2.425 mtrs.
Dimensions
P104 Measurement Units
This parameter sets the units you want to use for programming and display
Option
Description
1 = metres (Default)
All units of measure are
METRES
2 = cm
All units of measure are
CENTIMETRES
3 = mm
All units of measure are
MILLIMETRES
4 = feet
All units of measure are
FEET
5 = inches
All units of measure are
INCHES
P105 Empty Level
This parameter is to be set to the
maximum distance
from the
face
of the
transducer to the
empty point
, in
P104
Measurement
Units
. Note this
value affects span as well, (see important information below), so should be
set before span.
Important Information
When using the
dB Mach 3
the
empty distance
is measured from the end
of the
horn
to the
empty point
in
P104 Measurement Units
.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...