OCM Parameters
When Ultra Wizard = 3 Flow
PMD Setup
P700 Primary Measuring Device Type
This parameter is used to select the
type
of
Primary Measuring Device
and
enable additional parameters required to calculate the flow of the Primary
Measuring Device chosen (P701). Options are as follows:
0 = Off (Default)
1 = Exponent
2 = BS3680 Flume
3 = BS3680 Weir
4 = Area/Velocity (Optional)
5 = Special
6 = Universal
P701 Primary Measuring Device
Enter the Primary Measuring Device used.
If P700 = 1 (Exponent)
Select from the following options:
1 = Suppressed Rectangular Weir
2 = Cipolletti (Trapezoidal) Weir
3 = Venturi Flume
4 = Parshall Flume
5 = Leopold Lagco Flume
6 = V- notch Weir,
7 = Others
8 = Rectangular Weir with End Contractions
If P700 = 2 (BS 3680 Flume)
Select from the following options:
1 = Rectangular
2 = Rectangular with hump
3 = U-throated
4 = U-Throated with hump
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...