Page
207
mA Output Parameters
Range
P830 mA Range
This parameter determines the range of the mA output, from the following.
Option
Description
0= Off
mA output disabled.
1= 0 to 20 mA
mA output directly proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 0 mA. If
the reading is 100% the output is 20 mA.
2= 4 to 20 mA
(Default)
mA output directly proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 4 mA. If
the reading is 100% the output is 20 mA.
3= 20 to 0 mA
mA output inversely proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 0 mA.
4= 20 to 4 mA
mA output inversely proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 4 mA.
Operation
P831 mA Mode
This parameter determines how the ma Output relates to what is measured.
By
default,
it operates exactly the same as the display (
P100
), but it can be
set to operate as follows:
Option
Description
0 = Default
mA output relative to
Mode
P100
1 = Distance
mA output relative to
distance
.
2 = Level
mA output relative to
level
.
3 = Space
mA output is relative to
space
.
When Ultra Wizard = 1 Level/Volume
4 = Avg. Level
mA output is relative to the
average level
of
two points of measurement.
P100 = 4
5 = Volume
mA output is relative to volume
P100 = 5
6 = Vol. (Avg).
mA output is relative to the
average volume
of two points of measurement P
100 = 6
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...