![Pulsar ULTRA 5 Скачать руководство пользователя страница 170](http://html1.mh-extra.com/html/pulsar/ultra-5/ultra-5_instruction-manual_1624513170.webp)
Page 162
Control
P210, 220, 230, 240, 250 = 3 (Control)
When a relay is being set up as a
control
relay, the
second parameter
that
will be displayed in the menu determines its
function.
P211, P221, P231, P241, P251, Relay Function,
This function allows the relay to be assigned to specific
control
functions
(other than pumps and alarms) several of these functions work in relation to
time.
This can be used to activate devices based on elapsed time or running
cycles, such as a timed rake control to keep a ram lubricated if idle for long
periods, or flush valve operation.
Options
Description
0 = Off
Relay is always de-energised
1 = Time
Relay will
energise
“
ON
” after the
Cycle
time
that is set in Relay
Setpoint 2
(P2
1
4,
2
2
4, 2
3
4, 2
4
4, 2
5
4). And turns “
OFF
”,
de-
energises
, after the
On Time Period
that is
set in Relay
Setpoint 1
(P2
1
3, 2
2
3, 2
3
3, 2
4
3,
2
5
3)
When Ultra Wizard = 2 Pump/Differential
2 = Storm
Relay will
energise
“
ON
” when storm
conditions are in effect and,
de-energise
“
OFF
” when storm conditions cease. Two
setpoints are required, Upper Storm “
ON
”,
(P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3) and Lower Storm,
“
OFF
” (P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4).
This allows the relay to be used to activate a
device as a result of high levels such as a
storm condition e.g. opening a gate valve to
divert storm overflow into a holding vessel.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...