Page 36
Test Mode
Test mode is used to simulate the application and confirm that all parameters
and relay setpoints have been entered as expected. During simulation, there
is a choice of whether the relays will change state (hard simulation) or not
(soft simulation), but the LED’s will always change colour as programmed,
and the mA output will change in accordance to the chosen mode of
operation. If you wish to test the logic of the system that the
relays are
connected
to then select
hard simulation
, but if you
don’t wish to change
the relay state
, then select a
soft simulation
.
There are two simulation modes, automatic and manual. Automatic
simulation will move the level up and down between empty level or the pre-
determined
Start Level (P983)
and Pump/Control relay switch points, if
you wish to change the direction of the level movement e.g. to go beyond
relay setpoints, this can be done by using the arrow keys. In manual
simulation, using the arrow keys will allow you to move the level up and
down as required.
To enter simulation, first go to
program mode
. Using the menu system,
select menu item ‘
Test
’, then sub-menu item ‘
Simulation
’. Simply change
the value of the parameter
P980
to one of the following:
1= Manual soft simulation
2= Automatic soft simulation
3= Manual hard simulation
4= Automatic hard simulation
To return to program mode, press
CANCEL
and test mode will end.
When in
manual
simulation, by default test mode will move the level by
0.1m steps. Altering the
increment
(
P981
) will change this value.
In
automatic
mode, the rate at which the level moves up and down is set by
the
increment
(
P981)
in metres, the
rate
(
P982
) in minutes, which can be
changed to make the level move up and down faster. E.g. if
increment
(
P981
) is set for 0.1m and
rate
(
P982
) is set to 1 min then the level will
increase or decrease at a rate of 0.1m/min. To make the simulated level
move slower, decrease the value in
increment
(
P981
) or increase the value
in
rate
(
P982
). To make the simulated level move faster, increase the value
in
increment
(
P981
) or decrease the value in
rate
(
P982
).
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...