Item
Specifications
NX701-
£££
£
NX102-
£££
£
NX1P2-
££
££££
NJ501-
££££
NJ301-
££££
NJ101-
£££
£
Unit version
1.10 or later
Unit version
1.30 or later
Unit version
1.13 or later
Unit version
1.00 to 1.02
Unit version
1.03 or later
Unit version
1.10 or later
CIP service:
Tag data links
(cyclic commu-
nications)
Allowed communi-
cations bandwidth
per Unit
40,000
12,000
pps
3,000 pps
3,000 pps
Note: The
heartbeat is
included.
Note: The
heartbeat
and the CIP
Safety rout-
ing are in-
Note: The heartbeat is included.
Number of regis-
trable tags
256 per port (total of 512 with
two ports)
256
Tag types
Network vari-
ables
CIO, Work,
Holding, DM,
or EM Areas
cannot be
used.
Network vari-
ables
CIO, Work,
Holding, DM,
or EM Areas
can be used.
Network vari-
ables
CIO, Work,
Holding, or
DM Areas
can be used.
Network variables
CIO, Work, Holding, DM, or EM Areas can be
used.
Number of tags
per connection (=
1 tag set)
8 (7 tags when the tag set includes the Controller status)
Maximum link data
size per node
739,328
bytes
38,400 bytes
19,200 bytes
Maximum data
size per connec-
tion
600 bytes
Data concurrency is maintained within each connection.
Refer to
7-1-7 Concurrency of Tag Data Link Data
on page 7-12 for methods to maintain con-
currency.
Number of regis-
trable tag sets
256 per port
(1 connection
= 1 tag set)
(total of 512
with two
ports)
32 per port (1
connection =
1 tag set)
(total of 40
with two
32 (1 connection = 1 tag set)
Maximum size of 1
tag set
722 words
(The Control-
ler status
uses 1 word
when the tag
set includes
the Controller
status.)
300 words
(The Controller status uses 1 word when the tag set includes the Controller
status.)
Changing tag data
link parameters
when Controller is
in RUN mode
Multi-cast packet
filter
Supported
1 Introduction
1-9
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
1-3
Built-in EtherNet/IP Port
1
1-3-1
Specifications
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......