![Omron Sysmac NX1P2-10 1 Series Скачать руководство пользователя страница 93](http://html1.mh-extra.com/html/omron/sysmac-nx1p2-10-1-series/sysmac-nx1p2-10-1-series_user-manual_1633435093.webp)
Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP1_TDLinkOp-
nErr
CIP Communica-
tions1 Tag Data Link
Connection Failed
Indicates that establishing a tag data link
connection for CIP communications 1
failed.
TRUE: Establishing a tag data link con-
nection failed due to one of the following
causes.
•
The information registered for a target
node in the tag data link parameters is
different from the actual node informa-
tion.
•
There was no response from the re-
mote node.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
_EIP2_TDLinkOp-
nErr
CIP Communica-
tions2 Tag Data Link
Connection Failed
Indicates that establishing a tag data link
connection for CIP communications 2
failed.
TRUE: Establishing a tag data link con-
nection failed due to one of the following
causes.
•
The information registered for a target
node in the tag data link parameters is
different from the actual node informa-
tion.
•
There was no response from the re-
mote node.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
BOOL
TRUE or
FALSE
_EIP_TDLinkErr
Tag Data Link Com-
munications Error
NX-series CPU Units: Indicates that a
timeout occurred in a tag data link con-
nection for CIP communications 1.
TRUE: A timeout occurred.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that a
timeout occurred in a tag data link con-
nection.
TRUE: A timeout occurred.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
_EIP1_TDLinkErr
CIP Communica-
tions1 Tag Data Link
Communications Er-
ror
Indicates that a timeout occurred in a tag
data link connection for CIP communica-
tions 1.
TRUE: A timeout occurred.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-15
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined V
ariables
3
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......