Response Data Format
When the processing is successful
Parameter name
Data type
Description
Reply Service
USINT
Get current user error service response: BE hex
Reserved
USINT
Reserved: 00 hex
General Status
USINT
Code indicating normal: 00 hex
Size of Additional Status
USINT
Size of Additional Status: 00 hex
Error update count
UINT
Total count value of errors
Record size
UINT
Size of one record (Byte):0060 hex
Number of registered record
UINT
Number of registered records
Number of readout record
UINT
Number of readout records
User error record[0]
to
User error record[8]
Array of struct User
error record
User-defined error array
Stores data for the "Number of readout record" from
index 0 of the User error record. The remaining ele-
ments of the User error record array are not includ-
ed in the response data.
Example: When the "Number of readout record" is 3
and the response data includes the User error re-
cord array [0-2], the User error record array [3-8] is
not included in the response data.
For details of the specifications of the structure, re-
fer to User Error Record Structure.
When the processing failed
Parameter name
Data type
Description
Reply Service
USINT
Get current user error service response: BE hex
Reserved
USINT
Reserved: 00 hex
General Status
USINT
Current error code defined by CIP
Size of Additional Status
USINT
Size of Additional Status: 00 hex or 01 hex
Additional Status
UINT
Additional Status
*1.
When the General Status of the response code is 1F hex (Vendor specific error), becomes 01 hex.
*2.
This is stored only when the Size of Additional Status is 01 hex.
User Error Record Structure
Parameter name
Data type
Description
Index
UDINT
User-defined error index number
This number is assigned when system event logs
and access event logs are registered.
Event occurred time
ULINT
Error occurred time
Event source
UINT
Error source
Event priority
UINT
Error level
Event code
UDINT
Event code
Event priority details
UINT
Error level details
Reserved
UINT
Reserved
Additional information[0]
to
Additional information[39]
Array of BYTE
Attached information (system information) of event.
8 CIP Message Communications
8-70
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......