General
status
code (hex)
Status name
Description of status
02
Resource unavailable
Resources needed for the object to perform the requested service
were unavailable.
03
Invalid parameter value
See Status Code 20 hex.
04
Path segment error
The path segment identifier or the segment syntax was not under-
stood by the processing node. Path processing stops when a path
segment error occurs.
05
Path destination unknown
The path is referencing an object class, instance, or structure ele-
ment that is not known or is not contained in the processing node.
Path processing stops when a Path Destination Unknown Error oc-
curs.
06
Partial transfer
Only part of the expected data was transferred.
07
Connection lost
The message connection was lost.
08
Service not supported
The requested service was not supported or was not defined for this
object class/instance.
09
Invalid attribute value
Invalid attribute data was detected.
0A
Attribute list error
An attribute in the Get_Attribute_List or Set_Attribute_List response
has a non-zero status.
0B
Already in requested
mode/state
The object is already in the mode/state being requested by the serv-
ice.
0C
Object state conflict
The object cannot perform the requested service in its current mode/
state.
0D
Object already exists
The requested instance of object to be created already exists.
0E
Attribute not settable
A request to modify a non-modifiable attribute was received.
0F
Privilege violation
A permission/privilege check failed.
10
Device state conflict
The device's current mode/state prohibits the execution of the re-
quested service.
11
Reply data too large
The data to be transmitted in the response buffer is larger than the
allocated response buffer.
12
Fragmentation of a primi-
tive value
The service specified an operation that is going to fragment a primi-
tive data value, i.e. half a REAL data type.
13
Not enough data
The requested service did not supply enough data to perform the
specified operation.
14
Attribute not supported
The attribute specified in the request is not supported.
15
Too much data
The service supplied more data than was expected.
16
Object does not exist
An object that does not exist was specified for the requested serv-
ice.
17
Service fragmentation se-
quence not in progress
The fragmentation sequence for this service is not currently active
for this data.
18
No stored attribute data
The attribute data of this object was not saved prior to the requested
service.
19
Store operation failure
The attribute data of this object was not saved due to a failure dur-
ing the attempt.
1A
Routing failure (request
packet too large)
The service request packet was too large for transmission on a net-
work in the path to the destination. The routing device was forced to
abort the service.
1B
Routing failure (response
packet too large)
The service response packet was too large for transmission on a
network in the path from the destination. The routing device was
forced to abort the service.
8 CIP Message Communications
8-36
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......