The event log is immediately cleared after the service is successful. When it is executed for the Con-
troller, only the event log saved in the Controller is cleared. Event logs of slaves connected to the Con-
troller such as EtherCAT slaves are not cleared.
Request Data Format
Parameter name
Data type
Description
Service
USINT
Clear event log service: 3C hex
Request Path Size
USINT
Size of Request Path: 02 hex
Request Path
Padded EPATH
Request path: 2074 2401 hex
Class ID: 74 hex
Instance ID: 01 hex
Unit No
UINT
Unit number
0000 hex: Controller
0001 to 0020 hex: NX Unit
0021 hex or above: Not supported
Event log type
UINT
Event log type
0000 hex: System event log
0001 hex: Access event log
0003 hex: All types of the system event log, access
event log, user event log.
*1.
The User event log is valid only when the Controller is specified for the Unit number.
Response Data Format
When the processing is successful
Parameter name
Data type
Description
Reply Service
USINT
Clear event log service response: BC hex
Reserved
USINT
Reserved: 00 hex
General Status
USINT
Code indicating normal: 00 hex
Size of Additional Status
USINT
Size of Additional Status: 00 hex
When the processing failed
Parameter name
Data type
Description
Reply Service
USINT
Clear event log service response: BC hex
Reserved
USINT
Reserved: 00 hex
General Status
USINT
Current error code defined by CIP
Size of Additional Status
USINT
Size of Additional Status: 00 hex or 01 hex
Additional Status
UINT
Additional Status
*1.
When the General Status of the response code is 1F hex (Vendor specific error), becomes 01 hex.
*2.
This is stored only when the Size of Additional Status is 01 hex.
CIP Error Codes
General sta-
tus code
(hex)
Error name
Cause
02
Resource unavailable
Resources needed for the object to perform the requested
service were unavailable.
8 CIP Message Communications
8-67
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
8-5
CIP Object Services
8
8-5-3
NX Configuration Object (Class ID: 74 hex)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......