Additional Information
For an NJ-series CPU Unit, NX102 CPU Unit, and NX1P2 CPU Unit, when the local IP address
of the built-in EtherNet/IP port is set, the FINS node address is automatically set as shown be-
low. Note that the FINS node address is provided only to the NJ-series CPU Unit, NX102 CPU
Unit, and NX1P2 CPU Unit.
Example: Pairing an IP Address and an FINS Node Address with the Automatic generation
Method.
The same value as the host number is set.
Host number
(last 8 bits of the IP address)
After the IP address is obtained from the
BOOTP server, the node address of the
built-in EtherNet/IP FINS is set.
TCP/IP Settings Display
FINS Settings Display
When FINS node address are created automati-
cally, the FINS node address is the host ID and it
cannot be changed. It can be changed if you use
both methods or an IP address table method.
The FINS node address is required for FINS communications (e.g., to connect to the CX-Inte-
grator and other Support Software)
When the Automatic generation Method is selected, do not set the lower 8 bits of the IP ad-
dress to 000 or 255.
The NX102 CPU Unit has two EtherNet/IP ports. The FINS node address is set according to the
IP address of port 2.
4-2-3
Online Connection
Connect the Sysmac Studio online to the CPU Unit.
Types of Connection between the CPU Unit and Computer That
Runs the Sysmac Studio
The CPU Unit and the computer that runs Sysmac Studio are connected via USB or Ethernet as
shown below:
• USB Connection
Direct Connection via USB
USB connection
Sysmac Studio
*1. USB connection is not possible for the NX102
CPU Unit and NX1P2 CPU Unit.
• Ethernet Connection
4 Determining IP Addresses
4-8
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......