Attribute
ID
Parameter name
Description
Attrib-
ute
Read/write data
Data
type
Value
0D hex
HC Media Counters
Media counters for the com-
munications port.
Read
Struct
---
HCStatsAlignmentEr-
rors
The number of frames re-
ceived that were not octets in
length. This counter is the 64-
bit edition of Alignment Er-
rors.
ULINT
Reads the current value.
HCStatsFCSErrors
The number of frames re-
ceived that did not pass the
FCS check. This counter is
the 64-bit edition of FCS Er-
rors.
ULINT
Reads the current value.
HCStatsInternalMac-
TransmitErrors
The number of frames that
failed to be sent due to an in-
ternal MAC sublayer trans-
mission error. This counter is
the 64-bit edition of MAC
Transmit Errors.
ULINT
Reads the current value.
HCStatsFrameToo-
Longs
The number of frames re-
ceived that exceeded the
maximum allowed frame size.
This counter is the 64-bit edi-
tion of Frame Too Long.
ULINT
Reads the current value.
HCStatsInternalMa-
cReceiveErrors
The number of frames that
could not be received through
the interface due to an inter-
nal MAC sublayer reception
error. This counter is the 64-
bit edition of MAC Receive
Errors.
ULINT
Reads the current value.
HCStatsMacSymbolEr-
rors
The number of frames that
could not be received through
the interface due to an inter-
nal MAC sublayer rsymbol er-
ror.
ULINT
Reads the current value.
*1.
A CPU Unit with unit version 1.13 or later is required to use this attribute.
1. Interface Flag Details
Bit
Name
Description
0
LinkStatus
FALSE: The link is down. TRUE: The link is up.
1
Half/FullDuplex
FALSE: Half duplex TRUE: Full duplex
2 to 4
Negotiation Status
00 hex: Auto-negotiation is in progress.
01 hex: Auto-negotiation and speed detection failed.
02 hex: Auto-negotiation failed, but speed detection succeeded.
03 hex: Speed and duplex mode negotiation succeeded.
04 hex: Auto-negotiation was not attempted.
5
Manual Setting Requires
Speed
Always FALSE: Changes can be applied automatically.
6
Local Hardware Fault
Always FALSE
8 CIP Message Communications
8-80
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......