9-8
TCP/UDP Message Service
9-8-1
Outline of TCP/UDP Message Service
TCP/UDP message service provides a simple form of TCP/UDP socket communications intended for
access to CIP objects of the Controller from a system where EtherNet/IP is not supported. With this
function, you can change settings and perform I/O control for the Controller and Units connected to the
NX Bus. TCP/UDP message service can be performed simultaneously with tag data link communica-
tions.
This function is available only with NX102 CPU Units.
9-8-2
Specifications of TCP/UDP Message Service
Item
Specifications
Maximum number of clients which can
be connected simultaneously
32 (for UDP and TCP each)
Maximum message size
Request: 492 bytes
Response: 496 bytes
Maximum NX data output size
Maximum size of NX output data which can be written with the
TCP/UDP message service
488 bytes
Maximum NX data input size
Maximum size of NX input data which can be read with the TCP/UDP
message service
496 bytes
Port number
Port number used in the TCP/UDP message service
Default value: 64000 (decimal number)
9-8-3
Settings Required for TCP/UDP Message Service
When you use the TCP/UDP message service, you need to set the following unit settings.
The settings can be configured with the Sysmac Studio version 1.23 or higher.
Sysmac Studio Unit Settings
Tab Page
Setting
Setting condi-
tions
Setting range
Default
TCP/UDP message service
Use/Do not use
TCP/UDP message
service
Optional
Use/Do not use Do not use
Port 1-Port No.
Optional
64000
Port 2-Port No.
Optional
64000
*1.
When you use the TCP socket, the following port numbers are used by the system and cannot be set by the
user: 20, 23, 25, 80, 110, 9610, and 44818.
When you use the UDP socket, the following port numbers are used by the system and cannot be set by the
user: 25, 53, 68, 110, 2222, 2223, 2224, 9600, and 44818.
9-8-4
Command Format Specifications
9 Socket Service
9-31
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
9-8 TCP/UDP Message Service
9
9-8-1
Outline of TCP/UDP Message Service
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......