3-1
System-defined Variables Related to
the Built-in EtherNet/IP Port
You can use the system-defined variables that are provided for the built-in EtherNet/IP port in pro-
grams to check the status of the built-in EtherNet/IP port.
Checking for Errors in the Built-in EtherNet/IP Port
You can check for built-in EtherNet/IP port errors, Sysmac Studio setting errors, Network Configu-
rator setting errors, TCP/IP application errors (e.g., FTP or NTP), etc.
The following hierarchy is used. The system gives the error status at each level by logically ORing
the error status information in the next lower level.
Error status variable for
TCP/IP application function
Error status variable for
CIP communications
Error status variable for
communications port
Error status variable for EtherNet/IP Function Module
TCP Application Setting Error
NTP Server Connection Error
Identity Error
Tag Data Link Setting Error
Tag Data Link Connection Failed
Tag Data Link Communications Error
Multiple Switches ON Error
Tag Name Resolution Error
MAC Address Error
Communications Controller Error
IP Address Duplication Error
Basic Ethernet Setting Error
IP Address Setting Error
IP Route Table Error
BOOTP Server Error
DNS Server Connection Error
DNS Setting Error
_EIP_TcpAppErr
_EIP_TcpAppCfgErr
_EIP_NTPSrvErr
_EIP_IdentityErr
*1
_EIP_TDLinkCfgErr
*1
_EIP_TDLinkOpnErr
*1
_EIP_TDLinkErr
*1
_EIP_MultiSwONErr
*1
_EIP_TagAdrErr
*1
_EIP_CipErr
*1
_EIP_MacAdrErr
*1
_EIP_LanHwErr
*1
_EIP_IPAdrDupErr
*1
_EIP_EtnCfgErr
*1
_EIP_IPAdrCfgErr
*1
_EIP_IPRTblErr
_EIP_BootpErr
*1
_EIP_DNSSrvErr
_EIP_DNSCfgErr
*2
_EIP_PortErr
*1
_EIP_ErrSta
*1. Error status variables for errors related to NX-series CPU Units are provided individually for communica-
tions port 1 and communications port 2. You can use error status variables for communications port 2 with
the NX701 CPU Units and NX102 CPU Units only.
Refer to
Hierarchical Relationship of System-defined Variables Related to EtherNet/IP Errors in the NX-
series CPU Unit
*2. With the NJ-series CPU Unit, this variable can be used with the unit version 1.11 or later.
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-2
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......