Conditions
• Connections:
Example) Seventeen NJ501-1300 Units are connected to the network.
Each device has one 100-word tag for sending and sixteen 100-word tags for receiving, and ex-
changes data with each other.
The packet interval (RPI) for all the connections is set to 120 ms.
The IP addresses of the devices range from 192.168.250.1 to 192.168.250.17.
NJ501-1300: 17 Units
Connection RPI: 120 ms
17 network variables,
100 words each
192.168.250.1
NJ501-1300
NJ501-1300
NJ501-1300
NJ501-1300
192.168.250.3
192.168.250.17
192.168.250.2
100CH
100CH
100CH
100CH
IP address:
In_01_b
In_01_c
In_01_t
Send
Out_01_a
Send
Out_02_b
In_02_c
In_02_t
In_02_a
In_03_b
Send
Out_03_c
In_03_t
In_03_a
In_17_b
In_17_c
Send
Out_17_t
In_17_a
15 Communications Performance and Communications Load
15-17
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
15-2
Adjusting the Communications Load
15
15-2-5 RPI Setting Examples
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......