Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration
1
Configuration
2
Configuration
3
01
0117
Error code returned from target:
The tag set specified in the connection's
target variables does not exist.
Check whether
the originator
and target tag
sets and tags
are set correct-
ly.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
Check the orig-
inator's con-
nection set-
tings. Check
whether the
target tag sets
and tags are
set correctly.
01
011A
Error code generated by originator:
Connection could not be established be-
cause the buffer was full due to high traf-
fic.
Unexpected
network traffic
may have been
received.
Use the Ether-
net Information
Tab Page of
the Network
Configurator's
device monitor
to check the
bandwidth us-
age, and cor-
rect the load.
If there are pla-
ces where
broadcast
storms occur,
such as loop
connections in
the network
connection for-
mat, then cor-
rect them.
Unexpected
network traffic
may have been
received.
Use the Ether-
net Information
Tab Page of
the Network
Configurator's
device monitor
to check the
bandwidth us-
age, and cor-
rect the load.
If there are pla-
ces where
broadcast
storms occur,
such as loop
connections in
the network
connection for-
mat, then cor-
rect them.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
01
011B
Error code returned from target:
The RPI was set to a value that is below
the specifications.
This error does
not occur.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
Set the origina-
tor's RPI set-
ting to 1 ms or
greater.
01
0203
Error code generated by originator:
The connection timed out.
Tag data link communications from the target timed
out. Check the power supply and cable wiring of
the devices in the communications path, including
the target and switches. If performance has drop-
ped due to heavy traffic, change the performance
settings. For example, increase the timeout time or
RPI setting.
01
0204
Error code generated by originator:
The connection open process timed out.
There was no response from the target. Check the
power supply and cable wiring of the devices in the
communications path, including the target and
switches.
16 Troubleshooting
16-14
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......