Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration
1
Configuration
2
Configuration
3
01
0315
Error code returned from target:
There was a parameter error in the
frame used to open the connection.
This error does
not occur.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
Depends on
the originator's
specifications.
(Contact the
originator devi-
ce's manufac-
turer.)
01
0316
Error code returned from target:
There was a parameter error in the
frame used to close the connection.
This error does
not occur.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
Depends on
the originator's
specifications.
(Contact the
originator devi-
ce's manufac-
turer.)
01
031C
Error code generated by originator:
Some other error occurred.
This error does
not occur.
The originator
generates this
code when an
unsupported
response code
is returned
from the target
in reply to an
open request.
Depends on
the originator's
specifications.
(Contact the
originator devi-
ce's manufac-
turer.)
08
---
Error code returned from target:
There is no Forward Open or Large For-
ward Open service in the target device.
This error does
not occur.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
Depends on
the originator's
specifications.
(Contact the
originator devi-
ce's manufac-
turer.)
16 Troubleshooting
16-16
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......