Item
NX-series CPU Unit
NJ-series CPU Unit
CJ2M-CPU3
£
CS1W-EIP21
CJ1W-EIP21
CJ2H-CPU6
£
-
EIP
NX701
NX102
NX1P2
Unit version
Unit ver-
sion 1.00
to 1.02
Unit ver-
sion 1.03
or later
2.0
2.1 or lat-
er
Connec-
tion
Number of
connec-
tions
256
(total of
512 with
the two
ports)
32 (total of
64 with the
two ports)
32
32
256
Maximum
data size
per con-
nection
722 words
(Data con-
currency is
main-
tained at
each con-
nection.)
300 words
(Refer to
7-1-7 Concurrency of Tag Data Link Data
on page 7-12 for the conditions for maintaining da-
ta concurrency on a connection basis.)
20 words
640 words
252 or 722
words
(Data concurren-
cy is maintained
at each connec-
tion.)
(Data concurrency is
maintained at each con-
nection.)
Packet intervals (RPIs)
0.5 to
10,000 ms
in 0.5-ms
incre-
ments
1 to
10,000 ms
in 1-ms in-
crements
2 to
10,000 ms
in 1-ms in-
crements
10 to
10,000 ms
in 1-ms in-
crements
1 to
10,000 ms
in 1-ms in-
crements
1 to 10,000ms in 0.5-ms
increments
0.5 to 10,000 ms
in 0.5-ms incre-
ments
Communications band-
width used (pps)
40,000
12,000
3,000 pps
1,000 pps
3,000 pps
3,000 pps
6,000 pps
*1.
The maximum number of tags is given based on the following conditions.
•
All the tag sets contain eight tags each.
•
The maximum 32 tag sets are all used.
*2.
If the total number of registered tag sets exceeds 40, a Number of Tag Sets for Tag Data Links Exceeded (840E0000 hex) event oc-
curs.
*3.
To use data of 505 bytes or more, large forward open (an optional CIP specification) should be supported. The SYSMAC CS/CJ-series
Units support large forward open, and if you use nodes from other companies, confirm that the devices also support it.
*4.
The pps means “packets per second”, and indicates the number of packets that can be processed per second.
*5.
If the two built-in EtherNet/IP ports are used simultaneously, the given value is applied as the upper limit of the total bandwitdh of the
two ports.
Specifying Tags
When you assign a tag to a device, you can specify the device with its network variable or I/O
memory address. Some CPU Units, however, may not support both of these methods.
Communications with such CPU Units are possible though, regardless of whether the I/O memory
address or network variable is specified for the tag assignment.
The supported tag specification methods for each CPU Unit are listed in the table below.
Yes: Supported, No: Not supported
CPU Unit
Network Configura-
tor
hardware list name
Specifying
with network
variable
Specifying
with I/O memo-
ry address
EtherNet/IP Unit
NX-series CPU Unit
---
NX701
Yes
No
NX102
Yes
Yes
NX1P2
££££
Yes
Yes
NJ-series CPU Unit
---
NJ501-
££££
NJ301-
££££
NJ101
Yes
Yes
CJ1W-EIP21
CJ1W-EIP21 (NJ)
Yes
Yes
7 Tag Data Link Functions
7-87
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
7-4 T
ag Data Links with Other Models
7
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......