Additional Information
IP Router Table Setting Example
Set the following IP router table in node A to use tag data links or CIP message communica-
tions between node A and node B through the IP router.
If you set the IP router table and execute a communications instruction from node A to node B,
node A sends packets addressed to the gateway IP address (130.25.36.253).
Node A
IP router or NX-series CPU Unit
Node B
The host fields are set to 0 in the destination IP address.
130. 25. XX. XX
130. 26. XX. XX
130.25.36.253
130.26.2.254
Port Forward (NX102 CPU Unit)
Setting
Description
Default
IP Forward
Select whether to transfer IP packets between communications
ports.
Use
Packet Filter (NX102 CPU Unit)
Setting
Description
Default
Packet Filter
Select whether or not to set conditions of IP packets to be re-
ceived at the communications port.
Do not use
Pass Frame
Set the following items as the conditions of IP packets to be re-
ceived at the communications port. You can set the conditions
under which up to 32 packets are allowed to be received.
This setting is valid only when the
Use
Option is selected for
Packet Filter
.
---
Port
Select the communications port for which the Packet Filter is
used.
No. 1: Port 1
No. 2: Port 2
Specification Meth-
od
Method for specifying IP packets to be received.
IP address specification
any
No. 1: any
No. 2: any
IP Address
Specify an IP address that is allowed to be received.
None
Mask
Set the mask for the IP address allowed to be received. If you
select
IP address specification
for
Specification Method
,
255.255.255.255
is automatically set.
None
*1.
If you select
any
, packets from any IP addresses will be received.
5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
5-6
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......