7-1-3
Tag Data Link Functions and Specifications
The tag data link and performance specifications of the NJ/NX-series CPU Unit are given below.
Item
Specification
NX701-
£££
£
NX102-
£££
£
NX1P2-
£££
££££
NJ501-
££££
/NJ301-
£££
£
/NJ101-
££££
Unit version
1.00 to 1.02
Unit version
1.03 or later
Communications type
Standard EtherNet/IP implicit communications (connection-type cyclic commu-
nications)
Setting method
After you have set tags, tag sets, and connections with the Network Configura-
tor, you must download tag data link parameters to all devices on the
EtherNet/IP network. After the parameters are downloaded, the EtherNet/IP
Units are restarted to start the tag data links.
You can export network variables that you created on the Sysmac Studio to a
CSV file.
You can then import the file to the Network Configurator and assign the net-
work variables to the tags.
Tags
Supported variable
types
You can specify the following network variables as tags.
•
Global variables
Maximum number of
words per tag
722 words
(1,444 bytes)
300 words (600 bytes)
Maximum number of
tags
256
(total of 512 with two ports)
Tag
sets
Maximum number of
tags per tag set
8 (7 when Controller status is included)
Maximum number of
words per tag set
722 words
(1,444 bytes)
300 words (600 bytes)
Maximum number of
tag sets
256 (total of
512 with two
ports)
32 (total of 40
with two
32
Connections
Maximum
number of
connections
per unit: 512
(256 per port)
Maximum
number of
connections
per Unit: 64
(32 per port)
Maximum number of connections per Unit: 32
Connection type
Each connection can be set for 1-to-1 (unicast) or 1-to-N (multicast) communi-
cations.
Packet interval (RPI)
0.5 to 10,000
ms in 0.5-ms
increments
1 to 10,000
ms in 1-ms
increments
2 to 10,000
ms in 1-ms
increments
10 to 10,000
ms in 1-ms
increments
1 to 10,000
ms in 1-ms in-
crements
The packet interval can be set separately for each connection.
Allowed communications
bandwidth per Unit (pps)
40,000pps
12,000pps
3,000 pps
1,000 pps
3,000 pps
Note: The
heartbeat is
included.
Note: The
heartbeat and
the CIP Safe-
ty routing are
included.
Note: The heartbeat is included.
*1.
When you specify a specific I/O memory address for a tag for an NX102, NX1P2 or NJ-series CPU Unit,
create a variable with an AT specification for the I/O memory address on the Sysmac Studio, and then
7 Tag Data Link Functions
7-6
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......