Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP1_TagAdrErr
CIP Communica-
tions1 Tag Name
Resolution Error
Indicates that the tag resolution for CIP
communications 1 failed (i.e., the ad-
dress could not be identified from the tag
name).
TRUE: Tag resolution failed (i.e., the ad-
dress could not be identified from the tag
name). The following causes are possi-
ble.
•
The size of the network variable is dif-
ferent from the tag settings.
•
The I/O direction that is set in the tag
data link settings does not agree with
the I/O direction of the variable in the
CPU Unit.
•
There is no network variable in the
CPU Unit that corresponds to the tag
setting.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
BOOL
TRUE or
FALSE
_EIP2_TagAdrErr
CIP Communica-
tions2 Tag Name
Resolution Error
Indicates that the tag resolution for CIP
communications 2 failed (i.e., the ad-
dress could not be identified from the tag
name).
TRUE: Tag resolution failed (i.e., the ad-
dress could not be identified from the tag
name). The following causes are possi-
ble.
•
The size of the network variable is dif-
ferent from the tag settings.
•
The I/O direction that is set in the tag
data link settings does not agree with
the I/O direction of the variable in the
CPU Unit.
•
There is no network variable in the
CPU Unit that corresponds to the tag
setting.
FALSE: Other than the above.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
BOOL
TRUE or
FALSE
_EIP_MultiSwONErr
Multiple Switches ON
Error
NX-series CPU Units: Indicates that more
than one switch turned ON at the same
time in CIP communications 1.
TRUE: More than one data link start/stop
switch changed to TRUE at the same
time.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that more
than one switch turned ON at the same
time.
TRUE: More than one data link start/stop
switch changed to TRUE at the same
time.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-17
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined V
ariables
3
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......