Item
Specifications
NX701-
£££
£
NX102-
£££
£
NX1P2-
££
££££
NJ501-
££££
NJ301-
££££
NJ101-
£££
£
Unit version
1.10 or later
Unit version
1.30 or later
Unit version
1.13 or later
Unit version
1.00 to 1.02
Unit version
1.03 or later
Unit version
1.10 or later
CIP message
service:
Explicit
Class 3 (number of
connections)
Connections:
128 per port
(total of 256
with two
ports) (clients
plus server)
Connections:
32 per port
(total of 64
with two
ports) (clients
plus server)
Number of connections: 32 (clients plus servers)
UCMM (uncon-
nected)
Number of clients that can communicate at one time: 32 max.
Number of servers that can communicate at one time: 32 max.
CIP routing
Supported
CIP routing is supported for the following remote Units:
NX701-
££££
, NX102-
££££
, NX1P2-
££££
,
NJ501-
££££
, NJ301-
££££
, NJ101-
££££
,
CS1W-EIP21, CJ1W-EIP21,
CJ2H-CPU
££
-EIP, and CJ2M-CPU3
£
.
Using a combination of any Units above, communication can be extended up to a maximum of
8 levels.
SNMP
Agents
SNMPv1 or SNMPv2c
MIB
MIB-II
EtherNet/IP conformance test
Conforms to
CT11
Conforms to
CT14
Conforms to
CT13
NJ501: Conforms to CT12
NJ301: Conforms to CT14
Conforms to
CT14
Ethernet interface
10Base-T,
100Base-TX,
or 1000Base-
T
Auto negotia-
tion or fixed
settings
10Base-T or 100Base-TX
Auto negotiation or fixed settings
*1.
If tag data links are being used, use 100Base-TX or 1000Base-T.
*2.
Here, pps means “packets per second” and indicates the number of packets that can be processed in one second.
*3.
If the two built-in EtherNet/IP ports are used simultaneously, the maximum communications data size for two ports in total will be
reached.
*4.
An NX102 CPU Unit with unit version 1.31 or later is required to use the CIP Safety routing.
*5.
To use a data size of 505 bytes or larger, the system must support a large forward open (an optional CIP specification). The CS, CJ,
NJ, and NX-series Units support a large forward open, but before connecting to nodes of other companies, confirm that the devices
also support it.
*6.
When tag sets that exceed total of 40 are set, a Number of Tag Sets for Tag Data Links Exceeded (840E0000 hex) event occurs.
*7.
If the parameters of the built-in EtherNet/IP port are changed, the port is restarted. When other nodes are in communications with the
affected node, the communications will temporarily time out and automatically recover after the restart.
*8.
Because the built-in EtherNet/IP port is equipped with an IGMP client (version 2), unnecessary multicast packets can be filtered out by
an Ethernet switch that supports IGMP snooping.
*9.
The built-in EtherNet/IP port uses the TCP/UDP port numbers shown in the following table.
Do not set the same port number for more than one TCP/UDP service.
Service
Protocol
Port number
Remarks
EIP data links
UDP
2222
Fixed values
Used by system
UDP
2223, 2224
TCP
9610
CIP messages
TCP
44818
FTP client data transfer port
TCP
20
DNS client
TCP/UDP
53
BOOTP client
UDP
68
HTTP server
TCP
80
1 Introduction
1-10
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Содержание Sysmac NX1P2-10 1 Series
Страница 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 174: ...6 Testing Communications 6 4 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 354: ...8 CIP Message Communications 8 92 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 394: ...10 Modbus TCP Master Function 10 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Страница 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Страница 577: ......