113
Main Setup [200]
Section 11-2
Communication information
External Trip [25G]
Delay time starts counting when the fault is gone. When the time delay has
elapsed, the alarm will be reset if the function is active.
Communication information
External Trip Type [25H]
Select the preferred way to react to an alarm trip.
Communication information
Delay time starts counting when the fault is gone. When the time delay has
elapsed, the alarm will be reset if the function is active.
Modbus Instance no/
DeviceNet no:
43085
Profibus slot/index
168/244
EtherCAT index (hex)
4c0d
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
Off
1–3600
1–
3600
1–3600 s
Modbus Instance no/
DeviceNet no:
43080
Profibus slot/index
168/239
EtherCAT index (hex)
4c08
Fieldbus format
Long, 1=1 s
Modbus format
EInt
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/
DeviceNet no:
43081
Profibus slot/index
168/240
EtherCAT index (hex)
4c09
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
25G Ext Trip
Stp
Off
A
Trip
A
Off
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...