Main Setup [200]
Section 11-2
Note
The Motor Power value will always be stored as a 3 digit value in W up to 999
W and in kW for all higher powers.
Communication information
P
NOM
is the nominal VSD power.
Set the nominal motor current. If parallel motors set the sum of the motor cur-
rents.
Communication information
I
MOT
is the nominal VSD current.
!Warning
Do not connect motors with less than 25% of the nominal power of the VSD.
This may disrupt the control of the motor.
Set the nominal asynchronous motor speed.
!Warning
Do NOT enter a synchronous (no-load) motor speed.
Note
Maximum speed [343] is not automatically changed when the motor speed is
changed.
Note
Entering a wrong, too low value can cause a dangerous situation for the
driven application due to high speeds.
Modbus Instance no/
DeviceNet no:
43043
Profibus slot/index
168/202
EtherCAT index (hex)
4be3
Fieldbus format
Long,
1=1 W
Modbus format
EInt
Default:
I
MOT
(see note section 11-2-4, page 91)
Range:
25 - 150% x I
NOM
Modbus Instance no/
DeviceNet no:
43044
Profibus slot/index
168/203
EtherCAT index (hex)
4be4
Fieldbus format
Long,
1=0.1 A
Modbus format
EInt
224 Motor Curr
Stp M1:
(I
MOT
)A
A
Default:
n
MOT
(see note section 11-2-4, page 91)
Range:
50 - 18000 rpm
Resolution
1 rpm, 4 sign digits
225 Motor Speed
Stp M1: (n
MOT
)rpm
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...