195
I/Os and Virtual Connections [500]
Section 11-5
Communication information
Fig. 99
AnIn1 Enable [513A]
Parameter for enable/disable analogue input selection via digital inputs (DigIn
set to function AnIn Select).
Communication information
Parameter for setting the function of Analogue Input 2.
Same function as AnIn1 Func [511].
Modbus Instance no/
DeviceNet no:
43209
Profibus slot/index
169/113
EtherCAT index (hex)
4c89
Fieldbus format
Long, 1=0.001 s
Modbus format
EInt
Default:
On
On
0
AnIn1 is always active
!DigIn
1
AnIn1 is only active if the digital input is low.
DigIn
2
AnIn1 is only active if the digital input is high.
Modbus Instance no/
DeviceNet no:
AnIn1 43210
Profibus slot/index
AnIn1 169/114
EtherCAT index (hex)
4c8a
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Selection:
Same as in menu
[
]
AnIn change
100%
63%
Original input signal
Filtered AnIn signal
T
5 X T
On
A
514 AnIn2 Fc
Stp
Off
A