164
Process and Application Parameters [300]
Section 11-3
Communication information
Example:
Max Speed = 1500 rpm
Min Speed = 300 rpm
Upper Band = 10%
Start delay will be activated:
Range = Max Speed to Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 1500–120 = 1380 rpm
Fig. 85
Upper band
Lower Band [398]
If the speed of the master drive comes into the lower band an additional drive
will be stopped after a delay time. This delay time is set in the parameter Stop
Delay [39A].
Communication information
Example:
Max Speed = 1500 rpm
Min Speed = 300 rpm
Lower Band = 10%
Modbus Instance no/
DeviceNet no:
43167
Profibus slot/index
169/71
EtherCAT index (hex)
4c5f
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
10%
Range:
0-100% of total min speed to max speed
Modbus Instance no/
DeviceNet no:
43168
Profibus slot/index
169/72
EtherCAT index (hex)
4c60
Fieldbus format
Long, 1=1%
Modbus format
EInt
(NG_50-PC-12_1)
Flow/Pressure
Speed
Max
Min
Upper band
next pump starts
Start Delay [399]
A
10%
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...