218
Logical Functions and Timers [600]
Section 11-6
Fig. 103
Analogue Comparator 1 Level High [6112]
Selects the analogue comparator constant high level according to the
selected value in menu [6111].
The default value is 300.
No.
Description
1
The reference signal passes the Level LO value from below (positive edge),
the comparator CA1 output stays low, mode=RUN.
2
The reference signal passes the Level HI value from below (positive edge),
the comparator CA1 output is set high, mode=RUN.
3
The reference signal passes the threshold level of 4 mA, the motor speed will
now follow the reference signal.
T
During this period the motor speed will follow the reference signal.
4
The reference signal reaches the threshold level, motor speed is 0 rpm, mode
= RUN.
5
The reference signal passes the Level HI value from above (negative edge),
the comparator CA1 output stays high, mode =RUN.
6
The reference signal passes the Level LO value from above (negative edge),
the comparator CA1 output=STOP.
Default:
300 rpm
Range:
See min/max in table below.
Mode
Min
Max
Decimals
Process Val
Set by process settings [321] and [322]
3
Speed, rpm
0
Max speed
0
Torque, %
0
Max torque
0
1 2
3
4
5
6
20 mA
4 mA
3.2 mA
2.4 mA
CA1 Level HI = 16%
CA1 Level LO = 12%
Max speed
Reference signal AnIn1
CA1
Mode
RUN
STOP
T
t
6112 CA1 Level HI
Stp
300rpm
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...