194
I/Os and Virtual Connections [500]
Section 11-5
Communication information
Note
With AnIn Min, AnIn Max, AnIn Function Min and AnIn Function Max settings,
loss of feedback signals (e.g. voltage drop due to long sensor wiring) can be
compensated to ensure an accurate process control.
Example:
Process sensor is a sensor with the following specification:
Range:0–3 bar
Output:2–10 mA
Analogue input should be set up according to:
[512] AnIn1 Setup = User mA
[5131] AnIn1 Min = 2 mA
[5132] AnIn1 Max = 10 mA
[5134] AnIn1 Function Min = User-defined
[5135] AnIn1 VaMin = 0.000 bar
[5136] AnIn 1 Function Max = User-defined
[5137] AnIn1 VaMax = 3.000 bar
AnIn1 Operation [5138]
Communication information
If the input signal is unstable (e.g. fluctuation reference value), the filter can be
used to stabilize the signal. A change of the input signal will reach 63% on
AnIn1 within the set AnIn1 Filter time. After 5 times the set time, AnIn1 will
have reached 100% of the input change. See Fig. 99.
Modbus Instance no/
DeviceNet no:
43551
Profibus slot/index
170/200
EtherCAT index (hex)
4ddf
Fieldbus format
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
Modbus format
EInt
Default:
Add+
Add+
0
Analogue signal is added to selected function in menu
Sub-
1
Analogue signal is subtracted from selected function in
menu
[
].
Modbus Instance no/
DeviceNet no:
43208
Profibus slot/index
169/112
EtherCAT index (hex)
4c88
Fieldbus format
UInt
Modbus format
UInt
Default:
0.1 s
Range:
0.001 – 10.0 s
Add+
A
0.1s
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...