I/Os and Virtual Connections [500]
Section 11-5
Note
It is possible to set AnOut1 up as an inverted output signal by setting AnOut1
Min > AnOut1 Max. See Fig. 98.
AnOut1 Function Value Max [5337]
With AnOut1 Function VaMax you define a user-defined value for the signal.
Only visible when user-defined is selected in menu [5334].
Communication information
AnOut2 Function [534]
Sets the function for the Analogue Output 2.
Communication information
Preset scaling and offset of the output configuration for analogue output 2.
Fieldbus format
Long, 0.001
Modbus format
EInt
Default:
0.000
Range:
-10000.000–10000.000
Modbus Instance no/
DeviceNet no:
43555
Profibus slot/index
170/204
EtherCAT index (hex)
4de3
Fieldbus format
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
Modbus format
EInt
Default:
Torque
Selection:
Same as in menu
[
]
Modbus Instance no/
DeviceNet no:
43261
Profibus slot/index
169/165
EtherCAT index (hex)
4cbd
Fieldbus format
UInt
Modbus format
UInt
Default:
4-20mA
Selection:
Same as in menu
[
]
0.000
A
Torque
A
4-20mA
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...