79
Start and stop commands
Section 10-4
10-4 Start and stop commands
Set start and stop commands via serial communication.
.
Note
Bipolar mode is activated if both RunR and RunL is active.
10-5 Reference signal
When menu Reference Control [214] is set to “Com” the following parameter
data should be used:
10-5-1 Process value
It is also possible to send the Process value feedback signal over a bus (e.g.
from a process or temperature sensor) for use with PID Process controller
[380].
Set menu Process Source [321] to F(Bus). Use following parameter data for
the process value:
Modbus/DeviceNet
Instance number
Function
42901
Reset
42902
Run, active together with either RunR or RunL to
perform start.
42903
RunR
42904
RunL
Default
0
Range
-16384 to 16384
Corresponding to
-100% to 100% ref
Communication information
Modbus /DeviceNet
Instance number
42905
Profibus slot /Index
168/64
EtherCAT index (hex)
4b59
Fieldbus format
Int
Modbus format
Int
Default
0
Range
-16384 o 16384
Corresponding to
-100% to 100% ref
Communication information
Modbus /DeviceNet
Instance number
42906
Profibus slot /Index
168/65
EtherCAT index (hex)
4b5a
Fieldbus format
Int
Modbus format
Int
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...