165
Process and Application Parameters [300]
Section 11-3
Stop delay will be activated:
Range = Max Speed - Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 300 + 120 = 420 rpm
Fig. 86
Lower band
Start Delay [399]
This delay time must have elapsed before the next pump is started. A delay
time prevents the nervous switching of pumps.
Communication information
Stop Delay [39A]
This delay time must have elapsed before the 'top' pump is stopped. A delay
time prevents the nervous switching of pumps.
Communication information
Default:
0 s
Range:
0-999 s
Modbus Instance no/
DeviceNet no:
43169
Profibus slot/index
169/73
EtherCAT index (hex)
4c61
Fieldbus format
Long, 1=1s
Modbus format
EInt
Default:
0 s
Range:
0-999 s
Modbus Instance no/
DeviceNet no:
43170
Profibus slot/index
169/74
EtherCAT index (hex)
4c62
Fieldbus format
Long, 1=1 s
Modbus format
EInt
(NG_50-PC-13_1)
Speed
Max
Min
“top” pump stops
Lower band
Stop Delay [39A]
Flow/Pressure
0s
A
0s
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...