191
I/Os and Virtual Connections [500]
Section 11-5
Parameter to set the minimum value of the external reference signal. Only vis-
ible if [512] = User mA/V.
Communication information
Parameter to set the maximum value of the external reference signal. Only
visible if [512] = User mA/V.
Communication information
Special function: Inverted reference signal
If the AnIn minimum value is higher than the AnIn maximum value, the input
will act as an inverted reference input, see Fig. 98.
Fig. 98
Inverted reference
This menu is automatically displayed if AnIn1 Setup is set to User Bipol mA or
User Bipol V. The window will automatically show mA or V range according to
Default:
0 V/4.00 mA
Range:
0.00–20.00 mA
0–10.00 V
Modbus Instance no/
DeviceNet no:
43203
Profibus slot/index
169/107
EtherCAT index (hex)
4c83
Fieldbus format
Long
Modbus format
EInt
Default:
10.00 V/20.00 mA
Range:
0.00–20.00 mA
0–10.00 V
Modbus Instance no/
DeviceNet no:
43204
Profibus slot/index
169/108
EtherCAT index (hex)
4c84
Fieldbus format
Long
Modbus format
EInt
0V/4.00mA
A
5132 AnIn1 Max
Stp 10.0V/20.00mA
0
1 0 V
100 %
n
(NG_06-F25)
Invert
Ref
AnIn Min >
AnIn Max
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...