15 - 12
MELSEC-Q
15 TROUBLESHOOTING
Classification
of errors
Error
code
Error name
Error
Operation status at error occurrence
The hardware stroke limit (lower limit
signal RLS) is turned OFF during
operation.
The system stops with the setting
(deceleration stop/sudden stop) of the
detailed parameter 2 Sudden stop
selection (stop group 1).
(Note that the deceleration stop only
occurs during the manual pulse
generator operation.)
105
Hardware stroke
limit (–)
The start of an operation is
requested when the lower limit signal
(RLS) is OFF.
The system does not start.
106
Stop signal ON at
start
Start is requested when a stop signal
is turned ON.
The system does not start.
Common
107
READY OFF ON
during BUSY
The PLC READY signal is turned
from OFF to ON when BUSY signal
is turned ON.
The QD75 READY signal (X0) is not
turned ON.
201 Start at OP
When the OPR retry invalid is set,
the near-point dog machine OPR is
started with the OPR complete flag
turned ON.
The machine OPR is not started.
203
Dog detection timing
fault
The near-point dog signal is turned
OFF during the deceleration from an
OPR speed to a creep speed by the
near-point dog machine OPR.
204
OP detection timing
fault
The zero signal is turned OFF during
the deceleration from an OPR speed
to a creep speed by the stopper
method 2)-OPR.
205 Dwell time fault
A dwell time is passed during the
deceleration from a creep speed to a
OPR speed by the stopper method
1)-OPR.
The system stops with the setting
(deceleration stop/sudden stop) of the
detailed parameter 2 Sudden stop
selection (stop group 3).
(Note that the deceleration stop only
occurs during the manual pulse
generator operation.)
OPR
206
Count method
movement amount
fault
In the count method 1 and 2
machine OPR, a parameter "Setting
of movement amount after near-
point dog ON" is smaller than a
distance necessary for deceleration
stop from an OPR speed.
The machine OPR is not started.
Содержание Melsec-Q QD75D1
Страница 1: ......
Страница 2: ......
Страница 22: ...A 20 MEMO ...
Страница 24: ...MEMO ...
Страница 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Страница 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Страница 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Страница 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Страница 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Страница 292: ...MEMO ...
Страница 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Страница 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Страница 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Страница 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Страница 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Страница 693: ...Appendix 7 MELSEC Q APPENDICES Axis address mm inch degree pulse Axis address mm inch degree pulse ...
Страница 699: ...Appendix 13 MELSEC Q APPENDICES Initial value Axis 1 Axis 2 Axis 3 Axis 4 Remarks 0 0 0 1 1 0 0 0 0 0 0 300 11 0 0 ...
Страница 836: ...Appendix 150 MELSEC Q APPENDICES Appendix 14 External dimension drawing 1 QD75P1N Unit mm 23 4 27 4 98 90 46 ...
Страница 837: ...Appendix 151 MELSEC Q APPENDICES 2 QD75P2N Unit mm 23 27 4 90 4 98 46 3 QD75P4N 23 27 4 90 4 98 46 Unit mm ...
Страница 838: ...Appendix 152 MELSEC Q APPENDICES 4 QD75D1N 12 90 23 27 4 Unit mm 98 4 46 5 QD75D2N 90 23 27 4 12 98 4 46 Unit mm ...
Страница 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Страница 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Страница 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Страница 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Страница 857: ......
Страница 858: ......