3 SPECIFICATIONS AND FUNCTIONS
3.3.2 Details of input signals (QD75 CPU module)
The ON/OFF timing and conditions of the input signals are shown below.
Device
No.
Signal name
Details
X0 QD75
READY
ON:
READY
OFF: Not READY/
Watch dog
timer error
• When the PLC READY signal [Y0] turns from OFF to ON, the parameter setting
range is checked. If no error is found, this signal turns ON.
• When the PLC READY signal [Y0] turns OFF, this signal turns OFF.
• When watch dog timer error occurs, this signal turns OFF.
• This signal is used for interlock in a sequence program, etc.
PLC READY signal [Y0]
OFF
ON
QD75 READY signal [X0] OFF
ON
X1 Synchronization
flag
OFF: Module
access
disabled
ON: Module
access
enabled
• After the programmable controller is turned ON or the CPU module is reset, this
signal turns ON if the access from the CPU module to the QD75 is possible.
• When "Asynchronous" is selected in the module synchronization setting of the CPU
module, this signal can be used as interlock for the access from a sequence program
to the QD75.
X4
X5
X6
X7
Axis 1
Axis 2
Axis 3
Axis 4
M code ON OFF: M code is
not set
ON: M code is
set
• In the WITH mode, this signal turns ON when the positioning data operation is
started. In the AFTER mode, this signal turns ON when the positioning data
operation is completed.
• This signal turns OFF with the "
Cd.7
M code OFF request".
• When M code is not designated (when "
Da.10
M code" is "0"), this signal will
remain OFF.
• With using continuous path control for the positioning operation, the positioning will
continue even when this signal does not turn OFF. However, the warning "M CODE
ON SIGNAL START" (warning code: 503) will occur.
• When the PLC READY signal [Y0] turns OFF, the M code ON signal will also turn
OFF.
• If the operation is started while the M code is ON, the error "M CODE ON SIGNAL
START" (error code: 536) will occur.
X8
X9
XA
XB
Axis 1
Axis 2
Axis 3
Axis 4
Error
detection
OFF: No error
ON: Error
occurrence
• This signal turns ON when an error listed in Section 15.2 occurs, and turns OFF
when the error is reset on "
Cd.5
Axis error rest".
XC
XD
XE
XF
Axis 1
Axis 2
Axis 3
Axis 4
BUSY 1 OFF:
Not
BUSY
ON: BUSY
• This signal turns ON at the start of positioning, OPR or JOG operation. It turns OFF
when the "
Da.9
Dwell time" has passed after positioning stops. (This signal
remains ON during positioning.) This signal turns OFF when the positioning is
stopped with step operation.
• During manual pulse generator operation, this signal turns ON while the "
Cd.21
Manual pulse generator enable flag" is ON.
• This signal turns OFF at error completion or positioning stop.
X10
X11
X12
X13
Axis 1
Axis 2
Axis 3
Axis 4
Start
complete
OFF: Start
incomplete
ON: Start
complete
• This signal turns ON when the positioning start signal turns ON and the QD75 starts
the positioning process.
(The start complete signal also turns ON during OPR control.)
OFF
ON
OFF
ON
Positioning start signal [Y10]
Start complete signal [X10]
X14
X15
X16
X17
Axis 1
Axis 2
Axis 3
Axis 4
Positioning
complete
2
OFF: Positioning
incomplete
ON: Positioning
complete
• This signal turns ON for the time set in "
Pr.40
Positioning complete signal output
time" from the instant when the positioning control for each positioning data No. is
completed. For the interpolation control, the positioning completed signal of
interpolation axis turns ON during the time set to the reference axis.
(It does not turn ON when "
Pr.40
Positioning complete signal output time" is "0".)
• If positioning (including OPR), JOG/Inching operation, or manual pulse generator
operation is started while this signal is ON, the signal will turn OFF.
• This signal will not turn ON when speed control or positioning is canceled midway.
Содержание Melsec-Q QD75D1
Страница 1: ......
Страница 2: ......
Страница 22: ...A 20 MEMO ...
Страница 24: ...MEMO ...
Страница 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Страница 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Страница 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Страница 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Страница 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Страница 292: ...MEMO ...
Страница 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Страница 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Страница 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Страница 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Страница 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Страница 693: ...Appendix 7 MELSEC Q APPENDICES Axis address mm inch degree pulse Axis address mm inch degree pulse ...
Страница 699: ...Appendix 13 MELSEC Q APPENDICES Initial value Axis 1 Axis 2 Axis 3 Axis 4 Remarks 0 0 0 1 1 0 0 0 0 0 0 300 11 0 0 ...
Страница 836: ...Appendix 150 MELSEC Q APPENDICES Appendix 14 External dimension drawing 1 QD75P1N Unit mm 23 4 27 4 98 90 46 ...
Страница 837: ...Appendix 151 MELSEC Q APPENDICES 2 QD75P2N Unit mm 23 27 4 90 4 98 46 3 QD75P4N 23 27 4 90 4 98 46 Unit mm ...
Страница 838: ...Appendix 152 MELSEC Q APPENDICES 4 QD75D1N 12 90 23 27 4 Unit mm 98 4 46 5 QD75D2N 90 23 27 4 12 98 4 46 Unit mm ...
Страница 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Страница 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Страница 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Страница 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Страница 857: ......
Страница 858: ......