12 - 3
MELSEC-Q
12 CONTROL SUB FUNCTIONS
1 The near pass function is validated only when the machine of the standard specification carries out the position control
with the continuous path control mode.
It cannot be invalidated with parameters.
2 To carry out "torque limit", the "D/A conversion module" and a "drive unit capable of the torque limit command with an
analog voltage" must be prepared.
Sub function
Details
Absolute position restoration function 3
This function restores the absolute position of designated axis. By this
function, the OPR after power ON from OFF is not required once the OPR is
executed when the system operation is started.
Step function
This function temporarily stops the operation to confirm the positioning
operation during debugging, etc.
The operation can be stopped at each "automatic deceleration" or
"positioning data".
Skip function
This function stops the positioning being executed (decelerates to a stop)
when the skip signal is input, and carries out the next positioning.
M code output function
This function issues a sub work (clamp or drill stop, tool change, etc.)
according to the code No. (0 to 65535) set for each positioning data.
Teaching function
This function stores the address positioned with manual control into the
positioning address (
Da.6
Positioning address/movement amount) having
the designated positioning data No.
Command in-position
function
At each automatic deceleration, this function calculates the remaining
distance for the QD75 to reach the positioning stop position, and when the
value is less than the set value, sets the "command in-position flag" to 1.
When using another sub work before ending the control, use this function as
a trigger for the sub work.
Acceleration/deceleration
processing function
This function adjusts the control acceleration/deceleration.
(acceleration/deceleration time and curve).
Pre-reading start function This function shortens the virtual start time.
Deceleration start flag
function
Function that turns ON the flag when the constant speed status or
acceleration status switches to the deceleration status during position
control, whose operation pattern is "Positioning complete", to make the stop
timing known.
Other functions
Stop command processing
for deceleration stop
function
Function that selects a deceleration curve when a stop cause occurs during
deceleration stop processing to speed 0.
3 "The 16-point input module", "16-point output module", and "the drive unit capable of configuring an absolute position
detection system (, which is a Mitsubishi General-Purpose AC Servo and has an absolute position detection function
(absolute position data transference protocol) equivalent to that of MR-J3- A)" are required to execute the "absolute
position restoration function".
Содержание Melsec-Q QD75D1
Страница 1: ......
Страница 2: ......
Страница 22: ...A 20 MEMO ...
Страница 24: ...MEMO ...
Страница 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Страница 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Страница 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Страница 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Страница 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Страница 292: ...MEMO ...
Страница 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Страница 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Страница 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Страница 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Страница 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Страница 693: ...Appendix 7 MELSEC Q APPENDICES Axis address mm inch degree pulse Axis address mm inch degree pulse ...
Страница 699: ...Appendix 13 MELSEC Q APPENDICES Initial value Axis 1 Axis 2 Axis 3 Axis 4 Remarks 0 0 0 1 1 0 0 0 0 0 0 300 11 0 0 ...
Страница 836: ...Appendix 150 MELSEC Q APPENDICES Appendix 14 External dimension drawing 1 QD75P1N Unit mm 23 4 27 4 98 90 46 ...
Страница 837: ...Appendix 151 MELSEC Q APPENDICES 2 QD75P2N Unit mm 23 27 4 90 4 98 46 3 QD75P4N 23 27 4 90 4 98 46 Unit mm ...
Страница 838: ...Appendix 152 MELSEC Q APPENDICES 4 QD75D1N 12 90 23 27 4 Unit mm 98 4 46 5 QD75D2N 90 23 27 4 12 98 4 46 Unit mm ...
Страница 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Страница 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Страница 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Страница 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Страница 857: ......
Страница 858: ......