[3-3 Functions of the Major Components of Outdoor Unit ]
- 78 -
HWE1314A
GB
3-3
Functions of the Major Components of Outdoor Unit
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Com-
pressor
MC1
(Comp1)
Adjusts the amount of circulating
refrigerant by adjusting the operat-
ing frequency based on the oper-
ating pressure data
(E)200 - (E)250 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.72Ω
(E)300 - (E)350 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.32Ω
(E)P400 - (E)P450, P500
models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.3Ω
EP500 models
Low-pressure shell scroll
compressor
wirewound resistance
20°C [68°F] : 0.43Ω
High
pres-
sure
sensor
63HS1
1) Detects high pressure
2) Regulates frequency and pro-
vides high-pressure protec-
tion
Low
pres-
sure
sensor
63LS
1) Detects low pressure
2) Provides low-pressure pro-
tection
Pres-
sure
switch
63H1
1) Detects high pressure
2) Provides high-pressure pro-
tection
4.15MPa[601psi] OFF set-
ting
Thermis-
tor
TH4
(Discharge)
1) Detects discharge air temper-
ature
2) Provides high-pressure pro-
tection
Degrees Celsius
Resistance check
0°C[32°F] :698 kΩ
10°C[50°F] :413 kΩ
20°C[68°F] :250 kΩ
30°C[86°F] :160 kΩ
40°C[104°F] :104 kΩ
50°C[122°F] : 70 kΩ
60°C[140°F] : 48 kΩ
70°C[158°F] : 34 kΩ
80°C[176°F] : 24 kΩ
90°C[194°F] :17.5 kΩ
100°C[212°F] :13.0 kΩ
110°C[230°F] : 9.8 kΩ
Pressure
0~4.15 MPa [601psi]
Vout 0.5~3.5V
0.071V/0.098 MPa [14psi]
Pressure [MPa]
=1.38 x Vout [V]-0.69
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
63HS1
1
1 2 3
2
3
Pressure
0~1.7 MPa [247psi]
Vout 0.5~3.5V
0.173V/0.098 MPa [14psi]
Pressure [MPa]
=0.566 x Vout [V] - 0.283
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
GND (Black)
Vout (White)
Vcc (DC5V) (Red)
Con-
nector
63LS
1
1 2 3
2
3
R = 7.465k
120
R = 4057
R =
7.465
25/120
t
4057 273 t
1
393
1
exp
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...