[5-2 Outdoor Unit Control ]
- 150 -
HWE1314A
GB
5-2-16
Operation Mode
(1) Indoor unit operation mode
The operation mode can be selected from the following 6 modes using the remote controller.
(2) Outdoor unit operation mode
When units in cooing and heating coexist, the operation mode (cooling main mode or heating main mode) will be determined,
based on the refrigerant pressure in the R2 refrigerant circuit and speed variation data.
(3) Operation pattern for automatic cooling/heating mode
When the automatic cooling/heating mode is selected from remote controller functions, the indoor temperature will be detect-
ed in pattern as shown in the figure below, and the operation mode (cooling or heating) will automatically be selected.
(4) Relationship between the operation mode and the load capacity (kW) (within a system)
1
Cooling mode
2
Heating mode
3
Dry mode
4
Automatic cooling/heating
mode
5
Fan mode
6
Stopping mode
1
Cooling only mode
All indoor units in operation are in cooling mode.
2
Heating only mode
All indoor units in operation are in heating mode.
3
Cooling main mode
Coexistence of units in cooling and heating modes.
4
Heating main mode
Coexistence of units in cooling and heating modes.
5
Stopping mode
All indoor units are in fan mode or stopping mode.
Cooling
Fan
Heating
Switches to cooling mode
Cooling operation under
Thermo-ON conditions
Set temperature
(Variable between 19 C and 28 C
[ 67 F and 83 F])
Heating operation under Thermo-ON conditions
Switches to heating mode
Fan
Temperature
rise
1.5 C
[3 F]
1.5 C
[3 F]
1 C [2 F]
1 C [2 F]
Cooling load
capacity
Heating load
capacity
+
Cooling load
capacity
Heating load
capacity
Heating load
capacity
+
Cooling load
capacity
100(%)
Cooling only
mode
Cooling main
mode
Heating main
mode
Total heat recovery mode
Heating only
mode
100(%)
Heating
load (%)
Heating load
X100 = Cooling
load (%)
=
Cooling load
X 100
0
0
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...