[2-10 Restrictions on Refrigerant Pipes ]
- 58 -
HWE1314A
GB
7) The maximum capacity of the indoor units that is connectable to the CMB-P-V-GB1 types of sub BC controllers is P350 or
below (when two GB1 type controllers are connected P350 or below for both combined) .
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016V-HB1 is P350 or below.
If at least one CMB-P1016V-HB1 unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P450 or below.
Restrictions on pipe length
[PURY-(E)P200, 250YLM]
[PURY-(E)P300, 350, 400, 450, 500YLM]
[PURY-P400, 450YSLM, (E)P500, 550YSLM]
[PURY-(E)P600, 650YSLM]
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
1000
900
800
700
600
500
400
300
200
10 20
30
40
50
60
70
80
90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
[PURY-(E)P700, 750, 800, 850, 900YSLM]
200
300
400
500
600
700
800
900
1000
10 20 30 40 50 60 70 80 90 100 110
Distance between outdoor unit and BC controller(m)
Total
extended
pipe
length
(m)
0
10
20
30
40
50
60
70
0
5
10
15
Piping length between the main
BC controller and indoor units (m[ft])
Vertical separation between the main BC controller and indoor units (m[ft])
The height difference and the pipe length between BC controller and indoor units
[32]
[16]
[32]
[49]
[64]
[98]
[131]
[164]
[196]
[229]
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...