[8-10 Troubleshooting Inverter Problems ]
- 339 -
HWE1314A
GB
8
Trou
ble
sho
oting
Bas
ed
on
Obse
rved
Sy
mpto
ms
8-10-2
Checking the Inverter Board Error Detection Circuit
8-10-3
Checking the Compressor for Ground Fault and Coil Resistance Problems
8-10-4
Checking the Inverter for Damage at No-Load
Items to be checked
Phenomena
Remedy
(1)
Remove power supply.
1)
Overcurrent error
Error code: 4250
Detail code: No. 101, 104, 105, 106, and
107
Replace the INV board.
(2)
Disconnect the inverter
output wire from the ter-
minals of the INV board
(SC-U, SC-V, SC-W).
2)
Logic error
Error code: 4220
Detail code: No. 111
Replace the INV board.
(3)
Apply power supply.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
(4)
Put the outdoor unit into
operation.
4)
IPM open
Error code: 5301
Detail code: No.119
Normal
Items to be checked
Phenomena
Remedy
Disconnect the compressor wir-
ing, and check the compressor
Meg, and coil resistance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
Check that there is no liquid refrigerant
in the compressor.
If there is none, replace the compres-
sor.
2)
Compressor coil resistance failure
Coil resistance value of 0.72 Ω
(20°C [68°F]): (E)P200, (E)P250 models
Coil resistance value of 0.32 Ω
(20°C [68°F]): (E)P300, (E)P350 models
Coil resistance value of 0.30 Ω
(20°C [68°F]): (E)P400, (E)P450 models
Coil resistance value of 0.43 Ω
(20°C [68°F]): (E)P500 model
Replace the compressor.
Items to be checked
Phenomena
Remedy
(1)
Remove power supply.
1)
Inverter-related problems are detected.
Connect the short-circuit connector to
CN6 or set SW001-1 to ON, and go to
8-10-2.
(2)
Disconnect the inverter
output wire from the ter-
minals of the INV board
(SC-U, SC-V, SC-W).
2)
Inverter voltage is not output at the termi-
nals (SC-U, SC-V, and SC-W)
Replace the INV board.
(3)
Disconnect the short-cir-
cuit connector from CN6
on the INV board.
3)
There is an voltage imbalance between
the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
(4)
Apply power supply.
(5)
Put the outdoor unit into
operation.
Check the inverter output
voltage after the inverter
output frequency has sta-
bilized.
4)
There is no voltage imbalance between
the wires.
Normal
* Reconnect the short-circuit connec-
tor to CN6 or restore SW001 to its orig-
inal setting after checking the voltage.
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...