[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
- 268 -
HWE1314A
GB
7-8-8
Error Code [6607] Error Source Address = Outdoor Unit (OC)
1. Error code definition
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
7-8-9
Error Code [6607] Error Source Address = BC Controller (BC)
1. Error code definition
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Incidental cause
1)
Turn off the power source of the outdoor unit, and
turn it on again.
(2)
Contact failure of transmission line of OC or IC
2)
If the error is accidental, it will run normally. If not,
check the causes (2) - (5).
(3)
Decrease of transmission line voltage/signal by exceed-
ing acceptable range of transmission wiring.
Farthest: 200 m [656ft] or less
Remote controller wiring:
10m [32ft] or less
(4)
Erroneous sizing of transmission line (Not within the
range below).
Wire diameter:
1.25mm
2
[AWG16] or more
(5)
Outdoor unit control board failure
Cause
Check method and remedy
(1)
Incidental cause
1)
Turn off the power to the outdoor unit and the BC
controller, leave them turned off for at least 5 min-
utes, and then turn them back on.
(2)
When BC controller address is changed or modified dur-
ing operation.
2)
If the error is accidental, it will run normally. If not,
check the causes (2) - (5).
(3)
Faulty or disconnected transmission wiring of BC control-
ler
(4)
Disconnected connector of BC controller (CN02)
(5)
Faulty control board of BC controller
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...